Selecting Varistor Clamping Voltage: Lower is not Better !
François D. Martzloff, Thomas F Leedy · 1989
Surge protective devices, such as varistors, are applied to protect sensitive load equipment against power-line surges. The need to provide low clamping voltage for protection of equipment with low inherent immunity must be balanced against the risk of premature aging of the protective device. Lower clamping voltage causes more frequent interventions of the protective device, accelerating its aging. The paper describes four possible causes of such premature aging, calling for a more careful and thus more reliable application of protective devices.