Measurement and Analysis of Electrical Field around Secondary Equipment of Electronic Transformer in Equivalent GIS Due to Switch Operation

Yuhao Chen, Yan‐Zhao Xie, Hui Kang, Lin Cheng, Hui Xiang, Zhiyuan Wang, Jie Guo, Jiangping Lu · 2022 4th International Conference on Power and Energy Technology (ICPET) · 2022

The radiated E-field around secondary equipment of electronic current transformer and electronic voltage transformer are measured using the developed 3-D E-field measurement system under switch on operation of an equivalent 330 kV GIS system. Based on the electrically small antenna and fiber-optic transmission technology, the designed measurement system has a wide response frequency band from 10 kHz to 400 MHz. The time-domain and frequency-domain of measured signals are analyzed respectively. Under the switch on operation with charge voltage 200 kV and load 200 pF load, the maximum E-field can reach 18.67 kV/m and the frequency domain component are mainly over megahertz.