Testing earth fault loop impedance

Brian Scaddan, Brian Scaddan · 2012

External loop impedance Ze The value of Ze is measured at the intake position on the supply side and with all main equipotential bonding disconnected. Unless the installation can be isolated from the supply, this test should not be carried out, as a potential shock risk will exist with the supply on and the main bonding disconnected.