Contribution to Tagg's methodology in the resistance measurement of earth-electrode systems at reduced distances

Adroaldo Raizer, Vilson Luiz Coelho, Wilson Valente, Carlos Iran Cardoso · 2015

The main challenge of this article is to show a feasible solution for measuring earth resistance at short distances, considering that in practical terms, such is the condition found in the great majority of urban substations. A field test with 4 grounding meshes with different geometric configurations was implemented and used in order to perform a great number of measurement tests. Based on all the data and the processing of the measurement results, a mathematical model called the Extended Tagg Method was developed in order to establish the correct distance to carry out the measurement of earth resistance at short distances. A discussion on the proposed method, as well as its analysis of accuracy and susceptibility in view of external interference is performed, as well as its validation in real substations.

Read the paper · More papers on PaperTik