Measurement of Transmission Loss Through Partition Walls

E. H. Bedell, Karl D. Swartzel · The Journal of the Acoustical Society of America · 1933

This paper reviews the theory and describes the method used at Bell Telephone Laboratories of measuring the transmission loss through partition walls. The partition to be tested is built into an opening between two adjacent but structurally isolated rooms. A loud speaker acts as a source of sound in one room and a portion of the sound energy is transmitted into the second room through the test partition. The transmission loss is taken as TL = L1 − L2 − 0 log10 (a2/A), where L1 and L2 are the intensity levels in the source and test room respectively, expressed in db, a2 is the absorption in the test room and A is the area of the partition. The levels L1 and L2 are measured and plotted with a moving coil microphone and an automatic level recorder, and a beat frequency oscillator is used as a source of tone so that the frequency may be varied continuously. Measurements with a continuous variation in frequency enable resonances in the partition to be much more easily and quickly detected than is possible when measurements are made at discrete frequency intervals. Both pure and frequency modulated tones have been used for the measurements. Results of measurements on a few partitions are given.