D0 Silicon Upgrad: D0 Silicon Cooling System

B. Squires · 1998

The cooling system design is not complete. This paper lays out the general design and some of the design calculations that have been performed up to this date. Further refinement will be performed. This is especially true in the piping layout, piping insulation and detector manifold areas. The silicon detector is cooled by means of a coolant in the beryllium channels that also act as the primary supporting device for the silicon ladders and wedges. The coolant is water with ethylene glycol added as a freezing point depressant. The glycol concentration in the coolant is 30% by weight resulting in a freezing point of approximately -15 C. If the water/glycol is not sufficient for maintaining the desired detector temperature the concentration of the water/glycol may be changed or an alternative coolant may be used.